XBC Diesel Engine Driven Fire Pump Specification

![]() |
Centrifugal Pump: |
| These Centrifugal Pumps are specially designed for | |
| fire-fighting purposes. | |
| *Pump Type | |
| □-Horizontal End Suction Type | |
| □-Horizontal Split Case Type | |
| □-Horizontal Multistage Type | |
![]() |
|
| *Max. Capacity: 400L/S (6300 US.GPM) | |
| *Max. Head: 250mt. (355 psi) | |
| *Work Pressure: 1.6 Mpa (4.0 Mpa on request) | |
| *Materials: | |
| Casing in Cast Iron; Impeller in Cast Iron(Bronze on request); | |
![]() |
Shaft in Alloy Steel(Stainless Steel on request); Shaft Sleeve |
| in Stainless Steel. | |
| *Shaft Seal: Adjustable Packing Gland. | |
| Diesel Engine: | |
| *4 Stroke Cycle, Direct Injection. | |
| *Close type water cooled with radiator and fan, or Open type with heat exchanger | |
| *12 V or 24 V Electric Starting. | |
| *Rated Speed: 1500 RPM~3000 RPM. | |
| *The
following accessory items shall also be furnished: |
|
| -Lube Oil Heater (Option) | |
| -Engine Jacket Water Heater | |
| -Exhaust Silencer | |
| -Flexible Exhaust Connector | |
| -Lead Acid Batteries. | |
| -Battery Rack | |
|
-Fuel Tank in welded steel plate installed at a height above |
|
| that of the diesel engine with fuel for 6 hours operation. | |
| Controller: | |
| Designed to provide completed Automatic; Manual operation | |
| of diesel engine driven fire pump. | |
| *Assemble with two units of Battery Charger | |
| *Supply Voltage: 220V AC | |
| *Contacts for remote alarm of: | |
|
-Pump Running |
|
|
-Low Suction Pressure |
|
| -Technical Inconveniences | |
| *Visual Indicators are provided for the following alarm: | |
| Battery Failure; Engine Overspeed; Low Oil Pressure; | |
| Low Fuel Level; High Lub. Oil Temp.; High Water Temp.. | |
| *Wall Mounting or Floor Mounting protection IP44. | |
| *Relay for Remote Start. | |
| Accessories: | |
| *Mechanical Coupling and Coupling Guard. | |
| *Suction and Discharge Gauges. | |
| *Base Plate. | |
| *Anti vibration joints and dampers (Option). |